Formula library

Relay Plug Setting Multiplier

\[PSM=\frac{I_f}{I_{pickup}}\]

Variables

PSMplug setting multiplier
Iffault current seen by the relay (A)
Ipickuprelay pickup current setting (A)

Description

What is this formula?


The Plug Setting Multiplier (PSM) indicates how many times the actual fault current exceeds the relay pickup current setting.


When to use it


Use this formula when configuring overcurrent relays, performing protection coordination studies, evaluating relay sensitivity, and analyzing fault-clearing performance.


Example


A protection relay has:


Fault current = 2500 A


Pickup current setting = 500 A


Formula:


PSM = If / Ipickup


Substitution:


PSM = 2500 / 500


Result:


PSM = 5


The relay sees a fault current equal to five times its pickup setting.


Applications


Overcurrent relay settings


Protection coordination studies


Distribution system protection


Substation protection design


Fault analysis


Note


PSM is widely used in inverse-time overcurrent protection. A higher PSM generally results in a shorter relay operating time. The exact relationship between PSM and operating time depends on the relay characteristic curve selected, such as IEC Standard Inverse, Very Inverse, or Extremely Inverse.